Field Reference

IMC Conduit

What Intermediate Metal Conduit Is and How to Count It

23 November 2026By Vini P.K.
imc-conduit-takeoff-animationIMC CONDUIT RUN TAKEN OFF90 ELBOWJUNCTION BOXCOUPLINGSTRAPTAKEOFF RUNNINGTAKEOFF COMPLETE1IN IMC36 FT10 FT LENGTHS4COUPLINGS390 ELBOWS1STRAPS5LOCKNUT + BUSHING1PRICED BOM READYEVERY LENGTH, FITTING AND SUPPORT COUNTED

Short Answer

IMC conduit, or intermediate metal conduit, is a threaded galvanized steel raceway with a wall thinner than rigid metal conduit (RMC) and heavier than electrical metallic tubing (EMT). It is covered by NEC Article 342, comes in 10-foot lengths with a coupling on one end, and is used on industrial jobs where wiring needs physical protection. On a takeoff, IMC is counted by trade size and length, with its couplings, elbows, fittings and supports.

NEC article
342
Trade sizes
1/2 inch to 4 inch
Standard length
10 ft with one coupling
Joined by
Threaded couplings and fittings
Field Reference · Electrical

IMC vs EMT vs RMC Conduit

How the three steel conduits used on industrial jobs compare, and what changes on the takeoff.

EMTIMCRMC
Full nameElectrical metallic tubingIntermediate metal conduitRigid metal conduit
NEC article358342344
WallThin, not threadedMedium, threadedHeaviest, threaded
Trade sizes1/2 to 4 inch1/2 to 4 inch1/2 to 6 inch
Joined withSet screw or compression couplingsThreaded couplingsThreaded couplings
Where threaded conduit is requiredNot allowedAllowedAllowed
On the takeoffLightest to buy and installLess steel than RMC, same fittingsMost material and labor per foot

NEC is the National Electrical Code, NFPA 70. Many industrial specifications call for RMC or IMC by area, so check the specification and the area classification drawings before pricing.

What Is IMC Conduit?

IMC electrical conduit is a steel raceway that protects wire and cable. The IMC conduit meaning is in the name: intermediate metal conduit sits between thin-wall EMT and heavy-wall RMC. Its wall is thinner than RMC, so it weighs less and costs less per foot, but it uses the same threads and fittings, and the NEC allows it in most of the same places as RMC.

IMC is galvanized on the outside and coated inside. On industrial jobs it shows up in exposed runs on pipe racks and structural steel, in process areas where conduit can be hit, and in hazardous areas where the specification calls for threaded conduit. Drawings and specifications may write it as IMC, intermediate metal conduit or intermediate metal conduit (IMC), and all of them mean the same pipe.

IMC Conduit Sizes and Fittings

IMC conduit sizes run from 1/2 inch to 4 inch trade size. Trade size is a name rather than a measurement, so IMC conduit dimensions such as outside diameter and wall thickness come from the manufacturer's table and UL 1242, the product standard. Branch circuits and control wiring often run in 3/4 IMC conduit or 1-inch conduit, while feeders run larger.

IMC conduit fittings use the same threads as RMC, so threaded couplings, elbows, conduit bodies and hubs fit both. Each 10-foot length ships with one coupling, so extra couplings are bought only for cut pieces.

EMT vs IMC Conduit

The choice between EMT vs IMC conduit usually comes from the specification. EMT is lighter, faster to install and joined with set screw or compression fittings, so it is common indoors where it will not be damaged. IMC conduit vs EMT comes down to protection, because IMC is threaded, stronger and suited to outdoor, exposed and hazardous areas. For an estimator, an IMC vs EMT conduit change on the same run changes the fittings, the threading labor and the price per foot.

IMC vs RMC is a closer call. Both are threaded and take the same fittings, but IMC has the thinner wall, so it is lighter to carry and hang. Some specifications allow either, and some call for RMC only.

What Gets Counted With Every IMC Run

ItemHow It Is Counted
ConduitBy trade size, in feet, then in 10-foot lengths
CouplingsOne per joint between lengths
Elbows90 and 45 degree elbows by size, or field bends
Conduit bodiesLBs, Ts and Cs by size and type
SupportsStraps or clamps at each support point, plus the strut and hardware they hang from
Box connectionsLocknuts and bushings, or hubs, at each end of the run
SealsSeal fittings where a run crosses a hazardous area boundary

Wire and cable pulled through the conduit are counted separately, by size and length, from the same runs.

How to Count IMC Conduit

10-foot lengths = total feet × (1 + waste allowance) ÷ 10, rounded up

Straps = total feet ÷ 10, rounded up, + one per run

The strap count follows the NEC rule for IMC, which generally calls for a support within 3 feet of each box or termination and at least every 10 feet along the run. Measure each run from box to box on the electrical plans, and add the drops and rises shown on the details, which plan views do not show.

IMC Conduit Takeoff Calculator

Put in the measured feet and the number of runs to get the 10-foot lengths, couplings and straps. The starting values are examples.

10-foot lengths26
Couplings23
Straps27

Straps assume a support every 10 feet and one near each end of a run. Elbows, conduit bodies, box fittings and seals are counted separately.

Common Mistakes on an IMC Takeoff

  • Measuring runs from plan views only and missing the drops and rises
  • Pricing EMT fittings on an IMC run
  • Leaving out conduit bodies, seals and hubs
  • Counting straps without the strut, rod and hardware they hang from
  • Missing the specification note that calls for IMC or RMC in certain areas

How The Takeoff AI Handles Conduit

The Takeoff AI estimates the full electrical and instrumentation (E&I) package, including power plans, single line diagrams, schedules and the specification. It measures every conduit run by size and type, counts elbows, conduit bodies, fittings, supports, boxes and devices, measures cable and cable tray, and prices the material takeoff (MTO) and labor takeoff (LTO) into a priced bill of materials (BOM) at your own rates. It also builds a 3D model from the 2D drawings.

It is trained on more than 1.2 million electrical and instrumentation drawings, and every quantity is highlighted on the sheet it came from with an accept or reject option. More than 157 electrical estimators say The Takeoff AI saves them 90% of their time.

Before you ask

Frequently Asked Questions

Short answers on IMC conduit and how it gets counted.

Intermediate metal conduit, a threaded galvanized steel raceway with a wall thinner than RMC and heavier than EMT, covered by NEC Article 342.

The Takeoff Handbook

Reference the Estimating Library

Price your bid before your competitors open the package.

Book a Demo