What Is a Damper Actuator?
HVAC damper actuators turn the damper shaft to control airflow, so a damper motor is what makes a damper part of the control system instead of a manual balancing device. A motorized damper actuator ships either mounted on the damper from the factory or loose for the controls contractor to mount on site. Damper actuators are rated by torque, in inch-pounds, and by the control signal they accept.
Electric vs Pneumatic Damper Actuators
An electric damper actuator runs on 24 or 120 volts and is the default on new work. A pneumatic damper actuator uses control air, which keeps it common in older buildings and in industrial plants that already run an air system, and it needs tubing and often a transducer to take an electric signal. An HVAC damper motor on a fire or smoke damper is a listed device and usually comes with the damper.
What Is a Motorized Damper?
A motorized damper is a damper and actuator sold or installed as one assembly. On a takeoff it shows up twice: the damper itself in the sheet metal scope, and the actuator, wiring and control points in the controls scope. Counting both from the same damper schedule keeps the two scopes from double counting or missing items.
How Damper Actuators Are Sized
Torque needed (in-lb) = damper area (sq ft) × torque per sq ft × safety factor
Actuators per damper = torque needed ÷ actuator torque rating, rounded up
The torque per square foot comes from the damper manufacturer and depends on blade type, seals and air velocity. Large dampers are often built in sections, each with its own actuator or tied together with a jackshaft.
Damper Actuator Sizing Calculator
Put in a damper size, the torque the damper maker lists per square foot, and the actuator rating to see how many actuators each damper needs. The starting values are examples.
Torque needed is area times torque per square foot times the safety factor. Large dampers are often split into sections with an actuator on each.
What Gets Counted for Each Damper Actuator
| Item | How It Is Counted |
|---|---|
| Actuators | Each, by type, voltage, torque and spring return |
| End switches | Each, where the sequence needs damper position proven |
| Transformers | Each 24 volt transformer and its circuit |
| Wiring and conduit | Feet from each actuator to its controller |
| Control points | Digital or analog outputs and inputs per actuator |
| Linkages and jackshafts | Each, on multi-section dampers |
Common Mistakes When Counting Damper Actuators
- Counting dampers in the sheet metal scope and missing their actuators
- Pricing non-spring return actuators where the sequence calls for spring return
- Using one actuator per damper on large multi-section dampers
- Missing end switches on outside air and smoke dampers
- Leaving out control air tubing on pneumatic actuators
How The Takeoff AI Handles Dampers and Ductwork
The Takeoff AI estimates the mechanical and HVAC drawings, schedules and specification, and takes off the ductwork end to end. It measures duct, counts every damper, actuator and duct fitting, gasket, bolt and weld, and prices the material takeoff (MTO) and labor takeoff (LTO) into a priced bill of materials (BOM) at your own rates. It also builds a 3D model from the 2D drawings of the duct runs.
Every quantity is highlighted on the sheet it came from, and it is trained on more than 1 million drawing sets and runs at 95% accuracy. 113 estimators say The Takeoff AI is the best mechanical estimating software they have used, and it helps them estimate projects in 3 to 4 hours that once took 40 to 50 hours. See it on the mechanical page.